Parameter lists SMA Solar Technology AG
154 SI5048-TEN093630 Technical Description
233# Grid Start
46 FedInCurAt Maximum AC
charging current
230 V / 50 Hz 16 A
220 V / 60 Hz 16 A
47 FedInCurRt Maximum AC
charging current
48 FedInCtl EctCur EctCur
IntCur
49 GdSocEna Activate the grid
request based on
SOC
Disable Enable Disable
Enable Disable
50 GdPwrEna Activate the grid
request based on
power
Disable Enable Disable
Enable Disable
Number Name Description displayed
value
Description Default
value
01 GdSocTm1Str SOC limit for switching on
the grid for time 1
40 %
02 GdSocTm1Stp SOC limit for switching off
the grid for time 1
80 %
03 GdSocTm2Str SOC limit for switching on
the grid for time 2
40 %
04 GdSocTm2Stp SOC limit for switching off
the grid for time 2
80 %
05 GdTm1Str Time 1 for grid request in
hh:mm:ss
Begin time 1, end time 2
06 GdTm2Str Time 2 for grid request in
hh:mm:ss
Begin time 2, end time 1
07 GdPwrStr Grid request starting
capacity
4 kW
08 GdPwrStp Grid request
disconnection power limit
2 kW
Number Name Description displayed
value
Description Default
value

Table of Contents