SMA Solar Technology AG Electrical Connection
Technical Description SI5048-TEN093630 33
6.2.3 Cable protection
In addition to the internal DC circuit breakers, install a separate, external fuse as close as possible to
the battery. Install a suitable fuse plug for the fuse according to the maximum specified DC current
(e.g NH1 at 250 A).
6.2.4 Connection
There is a "DC " and a "DC +" connection available for each ring cable lug (max. 70 m) for the
battery feed cables in the Sunny Island.
DANGER!
Risk of lethal electric shock! Death or serious burns.
If no external cable protection is available, observe the following:
Lay the DC cables so that they are ground- and short-circuit-proof.
If there are short-circuit currents of over 10,000 A, use an additional fuse.
DANGER!
Danger to life due to high voltages Death or serious burns.
Connect the external fuse and the battery cable to the battery only after all
installation work has been completed.