Parameter lists SMA Solar Technology AG
148 SI5048-TEN093630 Technical Description
19.2.2 Battery Settings (220#)
221# Battery Property
Number Name Description Value Description Default
value
01 BatTyp Battery type VRLA Closed lead acid
batteries with
immobilized
electrolyte in gel or
AGM
(Absorbent Glass
Mat Separator)
VRLA
FLA A sealed lead acid
battery with liquid
electrolyte
NiCd Nickel-cadmium
battery
02 BatCpyNom Nominal battery
capacity
(E:C10/U:C20)
100 Ah
03 BatVtgNom Nominal battery
voltage
VRLA 48 V
FLA 48 V
NiCd 45.6 V
04 BatTmpMax Maximum battery
temperature
40 °C
05 BatTmpStr Battery start
temperature following
stop due to
overtemperature
35 °C
06 BatWirRes Power resistor of the
battery connection in
mOhm

Table of Contents