SMA Solar Technology AG Parameter lists
Technical Description SI5048-TEN093630 155
234# Generator Control
09 GdStrChrgMod Charging start upon grid
connection
Off off Equal
Full Full charge
Equal Equalization
charge
Both Full and
equalization
charging
Number Name Description Value Description Default
value
01 GnVtgMin Minimum generator
voltage
172.5 V
02 GnVtgMax Maximum generator
voltage
250 V
03 GnCurNom Nominal generator
current
16 A
04 GnFrqNom Generator nominal
frequency at nominal
load
230 V / 50 Hz 50 Hz
220 V / 60 Hz 60 Hz
05 GnFrqMin Minimum generator
frequency
230 V / 50 Hz 44.64 Hz
220 V / 60 Hz 50 Hz
06 GnFrqMax Maximum generator
frequency
230 V / 50 Hz 60 Hz
220 V / 60 Hz 70 Hz
07 GnStrMod Generator interface Manual Manual Autostart
Autostart Automatic
GenMan Generator
Management Box
from SMA
Solar Technology
08 GnOpTmMin Minimum run time of the
generator
15 min
09 GnStpTmMin Minimum stop time of
the generator
15 min
10 GnCoolTm Cooling-down time of
the generator
5 min
11 GnErrStpTm Stop time of the
generator if there is a
fault
1 h
Number Name Description displayed
value
Description Default
value