133# Generator State
Number Name Description displayed
value
Description
01 GnDmdSrc Source for generator request: None No request
Bat Battery charge
state-dependent
Lod Load-dependent
Tim Time-controlled
Run1h Requested for 1 hour
Start Manual
ExtSrcReq Requested via an
external source
02 GnStt Generator state Off Off
Init Init
Ready Waiting for request
(ready)
Warm Warming up
Connect Connecting
Run Operation
Retry Restarting
Disconnect Disconnecting
Cool Cooling down
Lock Locked after
operation
Fail Error
FailLock Locked after error
03 GnRmgTm Remaining time of the generator
(Minimum running time in hours,
minutes and seconds)
04 GnRnStt Status generator feedback master Off off
On On