Parameter lists SMA Solar Technology AG
150 SI5048-TEN093630 Technical Description
223# Battery Protection Mode
224# Battery Silent Mode
Number Name Description displayed
value
Default value
01 BatPro1TmStr Starting time of the battery-
preservation mode (level 1)
22:00:00
hh:mm:ss
02 BatPro1TmStp End time of battery-preservation
mode (level 1)
06:00:00
hh:mm:ss
03 BatPro2TmStr Starting time of the battery-
preservation mode (level 2)
17:00:00
hh:mm:ss
04 BatPro2TmStp End time of battery-preservation
mode (level 2)
09:00:00
hh:mm:ss
05 BatPro1Soc Battery charge state for battery-
preservation mode level 1
0 % ... 70 % 20 %
06 BatPro2Soc Battery charge state for battery-
preservation mode level 2
0 % ... 70 % 15 %
07 BatPro3Soc Battery charge state for battery-
preservation mode level 3
0 % ... 70 % 10 %
Number Name Description Value Description Default
value
01 SilentEna Silent mode on the grid Disable Enable Disable
Enable Disable
02 SilentTmFlo Maximal time for float
charge until transfer into
silent
1 h ...
48 h
3 h
03 SilentTmMax Maximal time for silent
until transfer into float
charge
1 h ...
168 h
12 h