234# Generator Control
Number Name Description Value Explanation Default
Value
01 GnVtgMin Minimum generator
voltage
172.5 V
02 GnVtgMax Maximum generator
voltage
250 V
03 GnCurNom Nominal generator
current
16.0 A
04 GnFrqNom Generator nominal
frequency with nominal
load
230 V / 50 Hz 50.00 Hz
220 V / 60 Hz 60.00 Hz
05 GnFrqMin Minimum generator
frequency
230 V / 50 Hz 44.64 Hz
220 V / 60 Hz 50.00 Hz
06 GnFrqMax Maximum generator
frequency
230 V / 50 Hz 60.00 Hz
220 V / 60 Hz 70.00 Hz
07 GnStrMod Generator interface Manual Manual Autostart
Autostart Automatic
GenMan Generator
management box
from SMA Solar
Technology
08 GnOpTmMin Minimum run time of the
generator
15 min
09 GnStpTmMin Minimum stop time of
the generator
15 min
10 GnCoolTm Cooling-down time of
the generator
5 min
11 GnErrStpTm Stop time of generator
in case of errors
1 h
12 GnWarmTm Warm up time 60 sec
13 GnRvPwr Generator reverse
power (active power)
100 W
14 GnRvTm Permissible time for
reverse power/reverse
current
30 sec
15 GnCtlMod Generator regulation Cur Electricity Cur
CurFrq Frequency