send warning alarm signal and it will be displayed on LCD.
When the battery voltage of genset is higher than threshold, controller
will send warning alarm signal and it will be displayed on LCD.
When low coolant level input is active, controller will send warning alarm
signal and it will be displayed on LCD.
When sensor cannot be connected to corresponding port, controller will
send warning alarm signal and it will be displayed on LCD.
When sensor cannot be connected to corresponding port, controller will
send warning alarm signal and it will be displayed on LCD.
When genset running time is longer than maintenance time of user
setting, and the maintenance action is set as warning, controller will
send warning alarm signal and it will be displayed on LCD.
When the water/cylinder temperature of genset is higher than threshold
and Enabled High Temp. Stop Inhibited or Input High Temp. Stop
Inhibited is active, controller will send warning alarm signal and it will be
displayed on LCD.
When the oil pressure of genset is less than threshold and Enabled Low
Oil Pressure Stop Inhibited or Input Low Oil Pressure Stop Inhibited is
active, controller will send warning alarm signal and it will be displayed
on LCD.
When external warning input is active, controller will send warning alarm
signal and it will be displayed on LCD.
When Failed To Charge input of charger is active, controller will send
warning alarm signal and it will be displayed on LCD.
When the controller detects that the over power value (power is positive)
has exceeded the pre-set value and the action select “Warn”, it will send
a warning alarm.
When the controller receives warning signal from ECU via CAN it will
send a warning alarm.