Table 3 Data Measurement
Type
Name
Unit
Gen
Line Voltage
V
Phase Voltage
V
Frequency
Hz
Phase Sequence
°
Load
Current
A
Different phases and
total active power
kW
Reactive Power
kvar
Apparent Power
kVA
Power Factor
/
Gen Total Power
kWhkvarhkVAh
Two selectable displays
Load output percentage= (active power/rated power) ×100%
Load output percentage= (average load current/rated current) ×100%
Precision measure and display of various parameters of the engine:
Temp. (WT) °C/ °F
Oil pressure (OP) kPa/psi/bar
Fuel level (FL) %
Speed (SPD) r/min (RPM)
Battery Voltage (VB) V
Charger Voltage (VD) V
Accumulated running hours Up to 999999 hours
Accumulated start times Up to 999999 times
Control protection: automatic start/stop of genset, closing/opening and perfect failure display
and protection functions;
With ETS, idle speed control, pre-heat control, speed droop/raising control, all of them are relay
output;
Parameter setting: allow users to modify setting, the parameters cannot be lost even when
power off. Most of parameters can be set from the front panel, all parameters can be adjusted
via USB interface (or RS485 interface) of PC.;
A variety of temperature, pressure and fuel level sensor curves can be used directly, and can be
defined by users;
Multi conditions of crank disconnect (frequency, speed, oil pressure) can be selected;
Wide power supply range: DC(8~35)V, adapting to different starting battery volts;
Event log, RTC, scheduled start/stop (once a month/week/day can be set whether to take load
or not);
With maintenance function. Maintenance time or actions (warning or alarm shutdown) can be
set;
Add rubber gasket between shell and controller screen of the waterproof can reach IP65;
HGMS61D is fixed by metal fixing clips and HGMS61M is fixed with screws;
Modular design and pluggable terminal, compact structure and easy installation.