HMC6 Power Management Controller User Manual Page 47 of 87
No.
Items
Parameter Range
Default
Description
1: Enable
15
Set value
(90-150)%
130
16
Delay
(0.1-100.0)s
1.0
17
Alarm Type
(0-5)
2:Trip
18
Under Voltage
1 Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
19
Set value
(50-100)%
95
20
Delay
(0.1-100.0)s
5.0
21
Alarm Type
(0-5)
1:Warn
22
Under Voltage
2 Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
23
Set value
(50-100)%
80
24
Delay
(0.1-100.0)s
3.0
25
Alarm Type
(0-5)
2:Trip
26
Under Voltage
3 Set
Action
(0-1)
0: Disable
1: Enable
0:Disable
27
Set value
(50-100)%
70
28
Delay
(0.1-100.0)s
2.0
29
Alarm Type
(0-5)
2:Trip
30
Over
Frequency 1
Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
Setting value is busbar rated frequency’s
percentage, return value and delay value
can be set.
31
Set value
(100-130)%
105
32
Delay
(0.1-100.0)s
5.0
33
Alarm Type
(0-5)
1:Warn
34
Over
Frequency 2
Set
Action
(0-1)
0: Disable
1: Enable
1:Enable
35
Set value
(100-130)%
110
36
Delay
(0.1-100.0)s
8.0
37
Alarm Type
(0-5)
2:Trip
38
Over
Frequency 3
Set
Action
(0-1)
0: Disable
1: Enable
0:Disbale
39
Set value
(100-130)%
120
40
Delay
(0.1-100.0)s
6.0
41
Alarm Type
(0-5)
2:Trip
42
Under
Frequency 1
Action
(0-1)
0: Disable
1:Enable