HMC6 Power Management Controller User Manual Page 59 of 87
No.
Items
Parameter Range
Default
Description
Configuration
Configuration (0-20)
Output Minimum
Output Maximum
Configure Minimum
Configure
Maximum
2.0
10
0
500
and transducer output can only be chosen.
22.
AVR Transducer
Configuration
Transducer
Configuration (0-20)
Output Minimum
Output Maximum
Configure Minimum
Configure
Maximum
0
2.0
10
0
500
One of AVR analog voltage regulating output
and transducer output can only be chosen.
23.
HMP300 Enable
(0-1)
0: Disable
24.
(0.1~999.9)s
5.0
Alarm delay.
25.
Self-check
Abnormal Return to
Manual
(0-1)
0: Disable
It forces the controller into manual mode if
the self-check is abnormal.
26.
Engine Failure
Action
(0-5)
0: Lock
Types of effective alarm action for engine
fault input port.
27.
Controller Type
(0-1)
0
0: DG mode
1: SG mode
28.
SG Working Mode
(0-2)
0
0: Load receiving mode
1: Fixed power mode
2: Load sharing mode
29.
Restart During
Shutdown
(0-1)
0Disable
1Enable
0: Disable
When it is enabled, it can restart the unit.
30.
T54 Is Ready
(0-1)
0Disable
1Enable
0: Disable
When it is enabled, the function of Terminal
54 will change from Engine Fault Input‘ to
‘Unit is Ready Input’.