Chapter  7   Control,  Inspection  and  Cleaning 
 
7.2 Inspection and Cleaning  HRSH Series 
 
  7-6 
◼  Replacement of circulating fluid 
●  Replace the circulating fluid with new clean fluid periodically, or it may 
get algae or decompose. 
●  Circulating fluid to be supplied in the tank should satisfy the water 
quality specified in “Table 7-1: Quality criteria for clean water (tap 
water)”. 
●  Make sure that the concentration of ethylene glycol aqueous solution is 
15%+5/0 when 15% ethylene glycol solution is used, and when 40% 
ethylene glycol aqueous solution is used, the concentration is 40% +5/-
0. 
●  When using the Y strainer provided as an accessory for piping, clean 
the screen mesh inside the strainer at the same time as when replacing 
the circulating fluid. 
Ensure that there is no circulating fluid in the thermo-chiller, user's 
equipment, and piping. Remove the cap and take out the screen mesh 
inside, and clean the screen mesh with compressed air or detergent. 
Use caution not to damage the screen mesh. 
Do not use chlorine-based or such types of detergents or cleansers. 
Put the screen mesh that has been cleaned into the groove in the cap, 
and reassemble it to the body of the strainer.   
◼  Cleaning of the facility water system (Water cooled type) 
●  Clean the customer's facility water system and replace facility water. 
●  Facility water quality must satisfy the criteria specified in “Table 7-1 
Quality criteria for clean water (tap water)”