Alarm code list label 2pcs. (English 1, Japanese 1),
Operation Manual 2 copies (English 1, Japanese 1),
Y strainer (40 mesh) 25A, Barrel nipple 25A,
Anchor bracket 2 pcs. (including 6 pcs. of M8 bolts)
9
1: When the ambient temperature or circulating fluid temperature is 10
o
C or below, refer to "3.2.2 Operation at low ambient temperature or low
circulating fluid temperature".
2: Use fluid for circulating fluid that conforms to:
Clean water: Water Quality Standards of the Japan Refrigeration and Air Conditioning Industry Association (JRA GL-02-1994)
15 to 40% ethylene glycol aqueous solution: Diluted with clean water, without any additives such as antiseptics. (Refer to "3.2.2 Operation at low
ambient temperature or low circulating fluid temperature" for the concentration of the ethylene glycol aqueous solution.)
DI water (pure water): Electrical conductivity 1 μS/cm or more (electrical resistivity 1MΩ・cm or less)
3: (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid temperature: 20
o
C, (4) Circulating fluid flow rate: Rated flow
rate, (5) Power supply: 200 VAC
4: (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid flow rate: Rated flow rate, (4) Power supply: 200 VAC
5: (1) Ambient temperature: 32
o
C, (2) Circulating fluid: Clean water, (3) Circulating fluid temperature: 20
o
C, (4) Load: Refer to the cooling capacity
shown in the specification table, (5) Circulating fluid flow rate: Rated flow rate, (6) Power supply: 200 VAC, (7) Piping length: Minimum
6: With the pressure control function using an inverter. When the pressure control function is not being used, the pump power supply frequency
setting function can be used.
7: Required flow rate to maintain the cooling capacity. When the flow rate is lower than the rated flow, use a by-pass piping set.
8: To be prepared by the user. A specified earth leakage breaker is installed for option B, B1 and S “ With earth leakage breaker”.
9: The anchor brackets (including M8 bolts x 6 pcs.) are used for fixation with the skid when this product is packed. The anchor bolts are not attached.