15
EN
DIRIS B-10L - 551174A - SOCOMEC
4.4. Presentation of associated current sensors
Various types of current sensors can be connected to the DIRIS B-10L: solid core (TE), split core (TR/iTR) or exible (TF).
This makes the DIRIS B-10L suitable with all types of new or existing installations. A rapid RJ12 connection makes wiring
easy and reliable and prevents wiring errors. The DIRIS B-10L automatically recognises the type of sensor used and its
current rating.
This guarantees the overall accuracy of the DIRIS B-10L + current sensor measurement chain.
DIRIS
B-10L
Current sensors TE / TR/iTR / TF
Recommendations:
For connecting the current sensors, use SOCOMEC cables only: RJ12 straight, twisted pair, unshielded, 600 V,
-10°C / +70°C as per IEC 61010-1 version 3.0.
It is recommended that all the current sensors be installed in the same direction.
Connection cables for current sensors:
RJ12
connection
cables
Cable length (m)
0.1 0.2 0.3 0.5 1 2 3 5 10
50m reel + 100
connectors*
Number of
cables
Ref. Ref. Ref. Ref. Ref. Ref. Ref. Ref. Ref. Ref.
1 - - - - - - 4829 0606 4829 0602 4829 0603 4829 0601
3 4829 0580 4829 0581 4829 0582 4829 0595 4829 0583 4829 0584 - - - -
4 4829 0596 4829 0588 4829 0589 - - - -
6 4829 0590 4829 0591 4829 0592 4829 0597 4829 0593 4829 0594 - - - -
* When producing cables, do not exceed a maximum length of 10 metres.