EasyManua.ls Logo

socomec DIRIS B-10L - 11.1.4. Measuring Characteristics; 11.1.5. Communication Characteristics

socomec DIRIS B-10L
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
67
EN
DIRIS B-10L - 551174A - SOCOMEC
11.1.4. Measuring characteristics
Measurement accuracy
Accuracy
According to IEC 61557-12
PMD DD classification in association with specied current sensors (TE, TR /
iTR, TF)
Measuring energy and power
Active energy and active power accuracy
Class 0.2 DIRIS B-10L alone
Class 0.5 with TE, iTR and TF sensors
Class 1 with TR sensors
Accuracy of reactive energy Class 2 with TE, TR/iTR and TF sensors
Power factor measurement
Accuracy
Class 0.5 with TE, iTR and TF sensors
Class 1 with TR sensors
Voltage measurement
Characteristics of the network measured 50-300VAC (Ph/N) - 87-520VAC (Ph/Ph) - CAT III
Frequency range 45 - 65Hz
Frequency accuracy Class 0.02
Network type
Single-phase/ Two-phase / Two-phase with neutral / Three-phase / Three-
phase with neutral
Measurement by voltage transformer
Primary: 400 000 VAC
Secondary: 60, 100, 110, 173, 190VAC
Input consumption 0,1 VA
Permanent overload 300VAC Ph/N
Accuracy of voltage measurement Class 0.2
Connection
Removable spring-cage terminal block, 2 x 6positions,
0.5-2.5 mm² solid cable or 0.25-1.5 mm² stranded cable with ferrule
Measurement of currents
Number of current inputs 4
Associated current sensors
Solid TE, split-core TR /iTR, flexible TF current sensors
Accuracy
Class 0.2 DIRIS B-10L alone
Class 0.5 with TE, iTR and TF sensors
Class 1 with TR sensors
Connection Specific Socomec cable with RJ12 connectors
11.1.5. Communication characteristics
Link Wireless
Protocol LoRaWAN
Bandwidth 863 - 870 MHz
Use Europe
Port 2
Class Class C
Power Level 14 dBm
Version 1.0.3
Spreading Factor SF7 to SF12
Activation Method OTAA

Table of Contents