4.4.3. TF exible current sensors
The TF exible current sensors use the Rogowski principle, covering a wide current range without saturation.
Their exible design and easy opening system enables a quick installation inside electrical panels, making them particularly
well suited for adding measuring points in existing electrical installations, especially when space is limited.
The secure lock technology prevents non voluntary openings of the Rogowski rope. Thanks to the specic link, they are
recognised by the DIRIS B-10L and a high level of overall accuracy for the measurement chain is guaranteed.
4.4.3.1. Range
Six models are available, covering a large current range up to 6000 A with openings of different shapes and sizes. They
include a compact and self-supplied integrator, required to shape the current signal.
TF-40 TF-80 TF-120 TF-200 TF-300 TF-600
Ø (mm) 40 80 120 200 300 600
I nom. (a.c.)
100 … 400A 150 … 600A 400 … 2000A 600 … 4000A 1600 … 6000A 1600 … 6000A
Part number
4829 0573 4829 0574 4829 0575 4829 0576 4829 0577 4829 0578
4.4.3.2. Dimensions
Dimensions in/mm
TF-40 TF-80 TF-120 TF-200 TF-300 TF-600
Diameter D
1.57
40
3.15
80
4.72
120
7.87
200
11.81
300
23.62
600
Perimeter L
4.96
126
9.88
251
14.84
377
24.72
628
37.09
942
74.21
1885
Diameter X
0.28
7
0.33
8.4
Integrator
8.04 x 0.75 x 0.6
128 x 19 x 15
L
D
X
1000 1000