6.3.3. Connection to the electrical network and to the loads
The DIRISB-10L can be used on either single-phase, two-phase or three-phase networks.
Different loads will then be measured simultaneously, allowing great exibility in terms of where it is tted in the installation.
The loads are measured using several types of sensor (closed, split-core, exible) selected depending on the application. The
link between the DIRISB-10L and its associated sensors is performed using cables with RJ12 connectors. These connectors
enable rapid, trouble-free installation, in complete safety, with no risk of the connector being inverted, and also offers
automatic detection of the connected sensors.
In addition, the DIRISB-10L is able to identify the majority of load types to be measured: single-phase, three-phase with or
without neutral using 1, 2, 3 or 4 sensors for balanced or unbalanced loads. Several loads can be measured simultaneously.
The overall accuracy of the DIRIS B-10L + sensors measurement chain is guaranteed. To guarantee this accuracy,
SOCOMEC cables must be used for the current sensors.
6.3.3.1. Congurable loads based on the network type
The table below summarises the loads that it is possible to congure depending on the type of network at the installation.
Network type Configurable load
1P+N 1P+N – 1CT
2P 2P – 1CT
2P+N 2P+N – 2CT / 2P – 1CT / 1P+N – 1CT
3P* 3P – 3CT / 3P – 2CT / 3P – 1CT
3P+N 3P+N – 4CT / 3P+N – 3CT / 3P+N – 1CT / 3P – 3CT / 3P – 2CT / 3P – 1CT / 1P+N – 1CT
(*) Note: Single-phase loads cannot exist on a 3P network.
6.3.3.2. Description of the main network and load combinations
Legend:
3P+N – 4CT
I01 I02 I03 I04
N
V1 V2 V3 VN
(1)
L1
L2
L3
3 + N
B-10LB-10L
Three phase load
Current sensor (CT)
B-10L current
terminal
B-10L voltage terminal
Three phase + Neutral
network with 4 current
sensors
3
3
3
3
CT
Current sensor
Balanced load Unbalanced load
3
3
Balanced load