49
EN
DIRIS B-10L - 551174A - SOCOMEC
8.4. LoRaWAN to Ethernet Modbus TCP gateway
A LoRaWAN gateway allows you to format LoRaWAN measurement data and to communicate via Modbus TCP on an
Ethernet output.
DATALOG H
Ethernet
Ethernet
DIRIS B-10L
DIRIS B-10L
PLC
WEBVIEW-L
LoRa Gateway
Core network embedded
Modbus registers
The LoRaWAN gateway re-creates a Modbus table containing the different measurements from the DIRIS B-10L
General information
Dec address Hex address Words count description Data Type
1 1 4 DevEUI U64
5 5 1 Device reference ID U16
6 6 2 Last uplink U32
14 E 1 SF (Spreading Factor) U16
15 F 1 RSSI S16
16 10 1 SNR S16
20 14 1 Profile number U16
Energy meters – Load 1
• Prole 1 (Single-load – Energies)
• Prole 2 (Multi-load – Energies)
• Prole 3 (Multi-load – Energies production)
Dec address Hex address Words count Description Unit Data type Function Profile
4096 0x1000 1
Load status
0 : Disabled
1 : Enabled
- U16 READ 1/2/3
4097 0x1001 2
Date of last
instance
s DATETIME READ 1/2/3
4099 0x1003 4 Ea+ Wh 10
-1
U64 READ 1/2/3
4103 0x1007 4 Ea- Wh 10
-1
U64 READ 1/3
4107 0x100B 4 Er+ varh 10
-1
U64 READ 1/2
4111 0x100F 4 Er- varh 10
-1
U64 READ 1
4115 0x1013 4 Reserved - - -