68
EN
DIRIS B-10L - 551174A - SOCOMEC
11.1.6. Environmental characteristics
Operating temperature -10 … +70°C (IEC 60068-2-1/IEC 60068-2-2)
Storage temperature range -25...+85°C (IEC 60068-2-1/IEC 60068-2-2)
Operating humidity 97%RH (IEC 60068-2-30)
Operating altitude < 2,000 m
Vibration 1G from 10 to 100Hz
Rated impulse voltage IEC 60947-1 V. IMP: 6.4kV
Impact resistance Front panel: 5J - casing: 1J (IEC 61010-1 Ed 3.0)
11.1.7. Electromagnetic compatibility
Immunity to electrostatic discharges IEC 61000-4-2 LEVEL III
Immunity to radiated radio-frequency fields IEC 61000-4-3 LEVEL III
Immunity to electrical fast transients/bursts IEC 61000-4-4 LEVEL IV
Immunity to impulse waves IEC 61000-4-5 LEVEL IV
Immunity to conducted disturbances IEC 61000-4-6 LEVEL III
Immunity to power frequency magnetic fields IEC 61000-4-8 400A/m LEVEL IV
Conducted emissions CISPR11 Group1 - CLASS B
Radiated emissions CISPR11 Group1 - CLASS B
Immunity to voltage dips and short interruptions IEC 61000-4-11 LEVEL III
11.1.8. Safety
Safety Compliance with Low Voltage Directive 2014/35/EU of 26 February
2014 (IEC EN61010-1 & IEC EN61010-2- 030)
Insulation Installation category III (300VAC Ph/N), degree of pollution 2
11.1.9. Service life
MTTF (mean time to failure) > 100 years