44
EN
DIRIS B-10L - 551174A - SOCOMEC
Prole 3: Multi-load – Energies (consumption/production)
Data
Number
of words
Unit Comments
Type 0.5 - Always 2 for this profile
Profile number 0.25 - Always 3 for this profile
Profile version 0.25 - Always 1 for this profile
Date/Time 2 s
Number of seconds elapsed since 01/01/2000 00:00.
Remains at 0 as long as the date and time has not been written via
the LoRa network.
Ea+ Load 1 2 kWh
Ea- Load 1 2 kWh
Ea+ Load 2 2 kWh
Ea- Load 2 2 kWh
Ea+ Load 3 2 kWh
Ea- Load 3 2 kWh
Ea+ Load 4 2 kWh
Ea- Load 4 2 kWh
Pulse Meter 4 NA Native Input 1
Digital Inputs and
VirtualMonitor (iTR)
1 -
Bit field
Bit 0: Digital Input 1 (Native)
Bit 1: Digital Input 2 (Native)
Bit 2: Digital Input 1 (optional module 1)
Bit 3: Digital Input 2 (optional module 1)
Bit 4: Digital Input 1 (optional module 2)
Bit 5: Digital Input 2 (optional module 2)
Bit 6: Digital Input 1 (optional module 3)
Bit 7: Digital Input 2 (optional module 3)
Bit 8: Digital Input 1 (optional module 4)
Bit 9: Digital Input 2 (optional module 4)
Bit 10: Voltage Detection iTR1
Bit 11: Voltage Detection iTR2
Bit 12: Voltage Detection iTR3
Bit 13: Voltage Detection iTR4
Status change
counter
1 -
Half byte field:
4 bits: status change counter - Native Input 1
4 bits: status change counter - Native Input 2
4 bits: status change counter - Digital Input 1 (optional module 1)
4 bits: status change counter - Digital Input 2 (optional module 1)
TOTAL 25 (50 bytes)