Average measurements – Load 1
The following Modbus table can be used only if one of the following proles is selected:
• Prole 4 (Single-load Monitoring)
• Prole 5 (Multi-load Monitoring)
Dec address Hex address
Words
count
Description Unit Data type Function Profil
8192 0x2000 1
Load status
0 : Disabled
1 : Enabled
- U16 READ 4/5
8193 0x2001 2 Date of last instance s DATETIME READ 4/5
8195 0x2003 2 Average Total Active Power W S32 READ 4/5
8197 0x2005 2 Average Total Reactive Power var S32 READ 4/5
8199 0x2007 2 Average Total Apparent Power VA S32 READ 4
8201 0x2009 1 Average Total Power Factor - S16 READ 4
8202 0x200A 1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
- U16 READ 4
8203 0x200B 2 Average Current phase 1 mA S32 READ 4
8205 0x200D 2 Average Current phase 2 mA S32 READ 4
8207 0x200F 2 Average Current phase 3 mA S32 READ 4
8209 0x2011 2 Average Frequency mHz S32 READ 4
Average measurements – Load 2
The following Modbus table can be used only if one of the following proles is selected:
• Prole 5 (Multi-load Monitoring)
Dec address Hex address
Words
count
Description Unit Data type Function Profil
8256 0x2040 1
Load status
0 : Disabled
1 : Enabled
- U16 READ 4/5
8257 0x2041 2 Date of last instance s DATETIME READ 4/5
8259 0x2043 2 Average Total Active Power W S32 READ 4/5
8261 0x2045 2 Average Total Reactive Power var S32 READ 4/5
8263 0x2047 2 Average Total Apparent Power VA S32 READ 4
8265 0x2049 1 Average Total Power Factor - S16 READ 4
8266 0x204A 1
Average Power Factor Type
0 : N/A
1 : Lagging
2 : Leading
- U16 READ 4
8267 0x204B 2 Average Current phase 1 mA S32 READ 4
8269 0x204D 2 Average Current phase 2 mA S32 READ 4
8271 0x204F 2 Average Current phase 3 mA S32 READ 4
8273 0x2051 2 Average Frequency mHz S32 READ 4