10-40 kVA
MASTERYS IP+
MENU
8
PRESENT CONFIGURATIONS menu
A Parameter Description Allowed values
• BATTERY RECHARGE Sets the recharge voltage compensation value YES/NO
TEMP COMPENSATION according to the battery temperature (not present
with external battery cabinets.
• BACKFEED TYPE Sets the type of backfeed protection. DISABLE
BY-PASS-INPUT ALONE
BY-PASS-INPUT COMMON
• BATTERY TEST Sets the frequency rate of the battery test in days 0÷180
TEST EVERY XX DAYS (zero = do not perform the test).
• LAN IP STATICO Sets the static IP address of the LAN 255.255.255.255
XXX . XXX . XXX .XXX
• SERIAL LINK JBUS Sets the mimic panel jbus node 1÷15
SLAVE NUMBER
DATE AND TIME Sets the date and time DD/MM/YY HH:MM
• EXTENDED COMMAND Enables/Disables the mimic panel extended commands YES/NO
• REMOTE COMMAND Enables/disables the remote controls YES/NO
BUZZER Enables/Disables the buzzer YES/NO
LCD CONTRAST Sets the LCD display contrast 0/100
• STATISTICS PERIOD Indicates the time in weeks for the calculation of statistics 1÷10
• GSS TIME DELAY Sets the generator start up delay time (visible only when 1÷60 MINUTES
the GSS PCB is installed)
E-SERVICE TYPE Select e-service operating mode NONE, MODEM, SMS
E-SERVICE TELEPHONE Insert the phone number to call for e-service messages MAX 20 CHARACTERS
NUMBER