10-40 kVA
MASTERYS IP+
IP52 VERSION
PREVENTIVE MAINTENANCE.
Please also refer to paragraph 10.3.
The user is allowed ONLY to replace the front
door internal air lter. A spare part kit is avail-
able as options.
It is strongly recommended to replace the front
door internal air lters at least every 6 months,
but their wear can be increased by the environ-
mental conditions.
Any other maintenace operation on the equip-
ment must be only carried out by SOCOMEC
UPS personnel or by authorised support per-
sonnel.
Air lters
INSTALLATION PROCEDURES AND INSTRUCTIONS.
Please also refer to paragraph 3.6.
To ensure the IP52 protection, lead the power
cables as shown in the picture aside.
Not provided