SE15K SE16K SE17K SE25K SE27.6K SE33.3K Unit
Residual current
detector / Residual
Current step detector
300 / 30 mA
Grid supported
three phase
3 / N / PE (WYEwith Neutral) V
Inrush current AC
(Peak/ Duration)
3/ 20 3.1/ 20 4.2/ 20
Aac
(rms) /
ms
Maximum output
fault current
40 63 A
Power factor range
1 (adjustable from -0.9 to
+0.9)
1 (adjustable from -0.8 to
+0.8)
(1)
Total harmonic
distortion
< 3%
Protective class Class I
Utility monitoring,
islanding protection,
configurable Power
Factor, country
configurable
thresholds
Yes
Overvoltage category III
Input
Maximum DC power
(Module STC)
20250 21600 22950 33750 37250 45000 W
Transformer-less,
ungrounded
Yes
Maximum input
voltage
900 1000 Vdc
Nominal DC input
voltage
750 840 Vdc
Maximum input
current
22 23 23 37 40 40 Adc
Maximum back-feed
current
0 Adc
Reverse-polarity
protection
Yes
(1)
For SE27.6K - when set to Germany Power Factor is limited to 0.9.
-Three Phase System Installation Guide MAN-01-00505-1.2
90 Technical Specifications - Three Phase Inverters (Europe &APAC)