SE15K SE16K SE17K SE25K SE27.6K SE33.3K Unit
Ground-fault isolation
detection
700 kΩ Sensitivity
350 kΩ Sensitivity
(1)
Overvoltage category III
Maximum inverter
efficiency
98 98.3 98.1 %
European weighted
efficiency
97.6 97.7 98 %
Night-time power
consumption
< 2.5 < 4 W
Additional Features
Supported
communication
interfaces
2 x RS485, Ethernet, Built-in GSM (Optional)
Inverter
commissioning
With the SetApp mobile application using built-in Wi-Fi
station for local connection
RS485 Surge
Protection
Smart Energy
Management
Export Limitation
Arc Fault Protection Integrated, user configurable (according to UL1699B)
Rapid Shutdown
Optional
(2)
(Automatic upon AC grid disconnect)
DC Safety Unit (optional)
2-pole Disconnection N/A 1000V / 40A
DC Surge Protection N/A Type II, field replaceable
DC Fuses on Plus &
Minus
N/A Optional, 20A
Compliance N/A UTE-C15-712-1
Standard Compliance
Safety IEC-62103 (EN50178), IEC-62109, AS3100
Grid connection
standards
(3)
VDE-AR-N-4105, G59/3, AS-4777, EN 50438 , VDE 0126-
1-1, CEI-021,
BDEW, CEI-016
(4)
;
(1)
Where permitted by local regulations
(2)
Inverter with rapid shutdown part number: SExxK-RWROOBNN2; available for SE25K and SE27.6K
(3)
For all standards refer to the Certifications category in
http://www.solaredge.com/groups/support/downloads.
(4)
Models SE25K, SE27.6Kand SE33.3K only
Technical Specifications - Three Phase Inverters (Europe &APAC) 91
Three Phase System Installation Guide MAN-01-00505-1.2
Optional
(5)
(5)
Provided with the inverter in India only. For other countries an SPD plug-in can be purchased. Refer to
https://www.solaredge.com/sites/default/files/se_spd_plug_in_for_rs485_3ph_setapp_ds.pdf