2.10.8.2 FULL FLOATING HOT GAS BYPASS
compressor as it operates in full hot gas bypass mode. The valve is factory set and no adjustment should be
necessary. If adjustment is required, remove the adjustment cap from the end of the valve. Using a 5/16 in
Allen wrench, turn the valve clockwise to increase pressure or counterclockwise to lower the pressure.
CAUTION
Do not exceed 20 °F superheat. Exceeding this temperature may cause compressor failure.
The normal control setting for the quench valve is 20 °F superheat (when there is no call for cooling). The
valve is factory set and no adjustment should be necessary. If adjustment is required, remove the adjustment
cap from the valve. Turn the adjusting stem clockwise to increase superheat and counterclockwise to
decrease the superheat.