7 LCD Operation User Manual
52
When the grid is set to “EE” or “EG”, the reactive power regulation will be in PF
mode with the power factor of +0.90 (0.90 lagging).
Tab. 7-7 Grid Standard Description
Grid company Code
Company
AG
AusGrid, NSW
EE
Ergon Energy, QLD
PN
SA Power Networks,SA
PC
Powercor,VIC
WP
Western Power,WA
EG
Energex, QLD
Other
Company not mentioned above
Each grid standard code represents corresponding protective parameters that
have been preset before delivery. The parameters for “Other” are applicable to
Australian and compliant with the standard AS/NZS 4777.
The values listed in the following table are for your reference only. Please follow
the requirements of local grid standard.
Tab. 7-8 Protective Parameters of Grid Standards
Parameter
Other
(Default)
AG EE EG PN PC WP
Over-voltage
1-V
max
(V)
260.0
260.0
260.0
260.0
260.0
260.0
260.0
1-Time (s)
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2-V
max
(V)
265.0
265.0
265.0
265.0
265.0
265.0
265.0
2-Time (s)
0.20
0.20
0.20
0.20
0.20
0.20
0.20
Under-voltage
1-V
min
(V)
180.0
200.0
180.0
180.0
180.0
180.0
180.0
1-Time (s)
2.0
2.0
2.0
2.0
2.0
2.0
2.0
2-V
min
(V)
180.0
200.0
180.0
180.0
180.0
180.0
180.0
2-Time (s)
2.0
2.0
2.0
2.0
2.0
2.0
2.0
Over-frequency
1-F
max
(Hz)
52.00
52.00
52.00
52.00
52.00
52.00
51.50
1-Time (s)
0.20
0.20
0.20
0.20
0.20
0.20
0.20
2-F
max
(Hz)
52.00
52.00
52.00
52.00
52.00
52.00
51.50
2-Time (s)
0.20
0.20
0.20
0.20
0.20
0.20
0.20
Under-frequency
1-F
min
(Hz)
47.00
48.00
47.00
47.00
47.00
47.00
47.00
1-Time (s)
1.50
1.50
1.50
1.50
1.50
1.50
1.50
2-F
min
(Hz)
47.00
48.00
47.00
47.00
47.00
47.00
47.00
2-Time (s)
1.50
1.50
1.50
1.50
1.50
1.50
1.50
10-min voltage
1-V
10-min
(V)
255.0
255.0
255.0
257.0
258.0
255.0
258.0

Table of Contents