Settings for cooling functions on this page and the next:
Value Setting Factory
range settings
Operation mode Inactive/active Inactive
Cooling regulation CoolDX
Stepless 0-10 V Stepless 0-10 V
Stepless10-0 V
On/Off 1 step
On/Off 2 step
On/Off 3 step binary
COOL DXS
Periodic operation
Cooling relay 1 Inactive/pump/ Inactive
pump+valve/valve
Cooling relay 2 Inactive/pump/ Inactive
pump+valve/ valve
Exercise period 1 – 60 min.
3 min.
Interval 1 – 168 hrs. 24 hrs.
Regulation speed
between steps 0-600 sec 300 sec
Outdoor temperature limit
Step 1 0-25 °C 3 °C
Step 2 0-25 °C 5 °C
Step 3 0-25 °C 7 °C
Restart time 0-900 sec 480 sec
Cooling min air flow
Supply air 0-Max flow –
Extract air 0-Max flow –
Neutral zone 0-10 °C 2.0 °C
Cooling BOOST Inactive Inactive
Comfort
Economy
Sequence
Comfort+economy
Economy+ sequence
Start limit in
connection to
min supply air temp 2-10 °C 3 °C