12.5 Activated conditions of HBA
Condition
1. OUT1 is ON
2. Heater current is less the HBA set value
3. Condition1 and 2 continued more than 5 seconds
AL1 will be activated, if condition 1&2&3 are all “true”.
12.6 Remarks
¾ Available output(OUT1) type for HBA
I. Relay
II. Voltage pulse (SSR drive)
¾ Since HBA function uses AL1 as alarm relay, please set temperature alarms in AL2 or
AL3.