4-49
Group 17 Automatic Tuning Parameters
Code Parameter Name Setting Range Default Unit
Control Mode
Attribute
V/F SLV
PM
SLV
17-00
Mode Selection of
Automatic Tuning*
0:Rotation Auto-tuning
1:Static Auto-tuning
2:Stator Resistance Measurement
3:Reserved
4:Loop Tuning
5:Rotation Auto-tuning
Combination (item: 4+2+0)
6:Static Auto-tuning
Combination (item: 4+2+1)
V/F:2
SLV:6
- O O X
17-01
Motor Rated Output
Power
0.00~600.00
KVA kW O O X
17-02
Motor Rated Current 0.1~1200.0
KVA A O O X
17-03
Motor Rated Voltage
200V:50.0~240.0
220
V O O X
400V:100.0~480.0
440
17-04
Motor Rated Frequency 4.8~599.0
60.0 Hz O O X
17-05
Motor Rotated Speed 0~24000
KVA RPM O O X
17-06
Pole Number of Motor 2~16(Even)
4 Pole O O X
17-08
Motor no-load Voltage
200V:50~240
KVA V O O X
400V:100~480
17-09
Motor Excitation Current 0.01~600.00
KVA A X O X
17-10
Automatic Tuning Start
0:Disable
1:Enable
0 - O O X
17-11
Error History of
Automatic Tuning
0:No error
1:Motor data error
2:Stator resistance tuning error
3:Leakage induction tuning error
4:Rotor resistance tuning error
5:Mutual induction tuning error
6:DT Error
7:Encoder error
8:Motor’s acceleration error
9:Warning
0 - O O X
17-12
Proportion of Motor
Leakage Inductance
0.1~15.0
KVA % X O X
17-13
Motor Slip Frequency 0.10~20.00
KVA Hz X O X
17-14
Selection of Rotation
Auto-tuning
0: VF Rotation Auto-tuning
1: Vector Rotation Auto-tuning
0 - O O X
KVA:The default value of this parameter will be changed by different capacities of inverter
It is suggested that HD/ ND mode (00-27) be selected first before motor performs auto-tuning.
Note:The value of mode selection of automatic tuning is 6 (Static Auto-tuning Combination). When do
auto-tuning with no-load motor, it is suggested to select 17-00=5 (Rotation Auto-tuning Combination)