4-114
(20) Auto run mode enable (03-0X=18)
Digital input set to “18”, auto run mode function will be enabled, please refer to group 06.
(21) Speed Search 1 (from the maximum frequency) (03-0X=19)
(22) Energy saving enabled (03-0X=20)
Manual energy savings function is set with parameters 11-12 and 11-18, for the manual energy
saving operation, please refer to figure 4.3.88。
(23) Reset PID integral value to zero (03-0X=21)
(24) Counter Input 1 (03-0X=22)
When digital input set to “22”, the counter value will be added once when the digital input
from "OFF" to "ON" status.
(25) Counter Reset (03-0X=23)
Counter counts can be reset to 0 at any time by using an external input connected to one of the
multi-function inputs (S1~S6) and by setting the relevant parameter (03-00 ~03-05) to 23,
inverter will display “C0000”. Inverter can receive counter signal again when the reset signal is
removed.
(26) PLC Input (03-0X=24)
When anyone of the extermal terminals S1 to S6 set to 24 and turned on, the PLC program
inputs will be enabled.
(27) Pulse-In Width Measure (S3) (03-0X=25)
When one of S1~S6 (except S3) set to 25, it will switch pulse width measurement function
from S3. In this mode, the pulse input frequency range is 10Hz~200Hz, the other digital
input can not set to 26 (pulse input-frequency measurement)
(28) Pulse Input Frequency Measure (03-0X=26)
When one of S1~S6 (except S3) set to 26, it will switch pulse width measurement function
from S3. In this mode, the pulse input frequency range is 0.05kHz~25.00kHz, the other
digital input can not set to 25 (pulse input-width measurement)
Note:
The priority of digital input pulse input measurement function is higher than 03-30.