4-115
(29) Local/Romote selection (03-0X=27)
Switch the inverter frequency reference source between Local (keypad) or Remote (control
circuit terminals or RS485). Use parameter 00-05 (Main frequency command source selection)
and 00-02 (Run command selection) to select the remote source.
Local/Remote function can be set by one of digital inputs (S3~S6), and be switched by
03-03~03-05 which the parameter setting is to “27”.In 3 wire operation control, S1/S2/S3 are
reserved for run/stop/forward-reverse operation, please refer the table below.
Note:Local and remote mode only can be switched when inverter stop running.
Input Mode Frequency Reference & Run/Stop Command Source
ON
Local
mode
Frequency eference and Run-Stop from keypad.
LEDs SEQ and REF are off.
OFF
Remote
mode
Frequency reference source selected by parameter 00-05
and Run/Stop source selected by parameter 00-02
LEDs SEQ and REF are on.
(30) Local/Romote selection (03-0X=28)
In Remote mode, indicators of SEQ and REF are on; you can use terminals AI1 and AI2 to
control the frequency command, and use terminals S1, S2 or communication terminal RS-485
to control the operation command.
When one of 03-02~03-05=28 (Remote mode selection),inverter can switch between external
terminal source (S1~S6) or communication (RS-485) source. Please refer the figure 4.3.23。
Figure 4.3.23 Remote mode operation selection
(31) Jog Frequency Selection (03-0X=29)
When jog frequency selection is on, the inverter will depend on the parameter 00-18 (jog
frequency) as the command.
(32) DC Braking (03-0X=33)
When DC-Injection braking is enabled during start and stop of the inverter.
DC injection braking is disabled when a run or jog command is active.
Refer to the DC braking time diagram in Figure 4.3.24.