4-119
03- 07 UP/DOWN Keep Frequency Status after Stop Command
Range
【0】:When UP/DOWN is used, the preset frequency is held as the inverterstops,
and the UP/DOWN function is disable.
【1】:When UP/DOWN is used, the preset frequency is reset to 0 Hz as the
inverter stops.
【2】:When UP/DOWN is used, the preset frequency is held as the inverter
stops, and the UP/DOWN is available.
【3】:When acceleration is used, the output frequency will be updated.
03-07=0, When run signal is removed (Stop Command), the output frequency is stored in
parameter 05-01( Key pad Frequency).
03-07=1, when run command is removed, the output frequency of deceleration will be clear.
03-07=2, when run command is not available, the UP/DOWN command will be written into
frequency command.
03-07=3, when frequency command is used, then resend the run command, the frequency
command will be updated by operation frequency when you press UP/DOWN key.
03- 08 S1~S6 scan time confirmation
Range 1~200ms
Multifunction input terminal On/Off periods will be scanned for the number of cycles according to
the set value in parameter 03-08. If the signal status for ON or OFF period is less than the set
period it will be treated as noise.
Use this parameter if unstable input signal is expected, however setting long scan time periods
results in slower response times.
03- 09 S1~S4 switch type select
Range
xxx0b】:S1 A Contact xxx1b】:S1 B Contact
xx0xb】:S2 A Contact 【xx1xb】:S2 B Contact
x0xxb】:S3 A Contactx1xxb】:S3 B Contact
0xxxb】:S4 A Contact 【1xxxb】:S4 B Contact
03- 10 S5~S6 switch type select
Range
xxx0b】:S5 A Contact 【xxx1b】:S5 B Contact
xx0xb】:S6 A Contact 【xx1xb】:S6 B Contact
Parameter 03-09 and 03-10 selects the digital input type between a normally open and a normally
closed switch/contact.
Each bit of 03-09/03-10 presents an input:
03-09= 0
0 0 0 0 :normally open switch
s4 s3 s2 s1 1 :normally close switch
03-10= 0
0 0 0 0 :normally open switch
s6 s5 1 :normally close switch
Example:S1 and S2 wired to a normally closed contact/switch set 03- 09=0011
Note:
Do not set the operation command parameter 00-02 to terminal control before setting the digital
input type. Failure to comply may cause death or serious injury.