4-129
03-24 Output Under Current Detection
Range
【0】:Invalid
【1】:Valid
03-25 Output Under Current Detection Level
Range 【0~999.9】A
03-26 Output Under Current Detection Delay Time
Range 【0.0~655.34】 Sec
If 03-11=55, when output current ≦ 03-25, output relay is active.
When 03-25=0, the function will be disabled.
When output current lower than 03-25 for a preset time (03-26), output relay is active. The
delay time of output relay from ON to OFF is 100ms (constant).
The timing chart:
03-26
Fixed
100msec
03-25
03-11
Relay
ON
I (Loading current)
100%
T
Operation
Command
ON
Smaller than 03-26
Relay does not work