4-132
Group 04 Analog Signal Inputs / Analog Output
04- 00 Analog Input Signal Type
Range
【0】: AI1 0~10V / 0~20mA AI2 0~10V / 0~20mA
【1】: AI1 0~10V / 0~20mA AI2 2~10V / 4~20mA
【2】: AI1 2~10V / 4~20mA AI2 0~10V / 0~20mA
【3】: AI1 2~10V / 4~20mA AI2 2~10V / 4~20mA
04- 01 AI1 Signal Scaling and Filter Time
Range 【0.00~2.00】Sec
04- 02 AI1 Gain
Range 【0.0~1000.0】%
04- 03 AI1 Bias
Range 【-100~100.0】%
04- 05 AI1 Slope
Range
【0】:Positive
【1】:Negative
04- 06 AI2 Signal Scaling and Filter Time
Range
【0】:Positive
【1】:Negative
04- 07 AI2 Gain
Range 【0.0~1000.0】%
04- 08 AI2 Bias
Range 【-100.0~100.0】%
04- 10 AI2 Gain
Range
【0】:Positive
【1】:Negative
Refer to the follows for 04-00 AI input signal type
If AI1 is 0~10V, switch JP2 of control board to V, set parameter 04-00 to 0 or 1.
If AI1 is 2~10V, switch JP2 of control board to V, set parameter 04-00 to 2 or 3.
If AI1 is 0~20mA, switch JP2 of control board to I, set parameter 04-00 to 0 or 1.
If AI1 is 4~20mA, switch JP2 of control board to I, set parameter 04-00 to 2 or 3.
If AI2 is 0~10V, switch JP3 of control board to V, set parameter 04-00 to 1 or 3.
If AI2 is 2~10V, switch JP3 of control board to V, set parameter 04-00 to 2 or 4.
If AI2 is 0~20mA, switch JP3 of control board to I, set parameter 04-00 to 1 or 3.
If AI2 is 4~20mA, switch JP3 of control board to I, set parameter 04-00 to 2 or 4.
(1) Analog input level adjustment AI1/AI2(04-02, 04-03,04-07, 04-08)
Each input signal AI1 and AI2 has a separate gain and bias parameter associated.
Analog input signal AI1 can be adjusted with parameter 04-02 and 04-03. Analog input
signal AI2 can be adjusted with parameter 04-07 and 04-08.Refer the figure 4.3.35。