4-131
03-27=200Hz (Pulse Frequency)
03-28=100.0~1000% (Pulse Input Gain)
When PWM input with different duty, the ouput frequency of display will be different.
When 200Hz pulse with 50% duty, 00-12=60.00, 03-28=100.0, keypad display will be
50% ×60.00=30.00Hz,
When 200Hz pulse with 30% duty, 00-12=60.00, 03-28=200.0, keypad display will be
30% ×60.00 ×2=36.00Hz。
When 200Hz pulse with 15% duty, 00-12=599.00, 03-28=500.0, keypad display will be
15%×599.00×5.00=449.25Hz。
Note:
In this mode, the pulse input frequency range is 10Hz~200 Hz.
Pulse input only can select S3 terminal, also can use NPN or PNP connection.
PNP connection:
PLC pulse ourput (Y0) connects to S3 terminal, the common terminal of PLC pulse output connects
to external 24V terminal of inverter, it’s PNP connection.
NPN connection:
PLC pulse ourput (Y0) connects to S3 terminal, the common terminal of PLC pulse outputconnects
to external COM terminal of inverter, it’s PNP connection.
03-33
Pulse Input Bias
Range
【-100.0~100.0】%
03-34 Filter Time of Pulse Input
Range
【0.00~2.00】Sec
Refer to section 3.4 table 2 control terminals for details.
Refer to figure 4.3.27 for the pulse input specification.
Figure 4.3.27 Pulse input adjustment
Set Pulse Input Setup as Frequency Reference
(1) Set parameter 00-05 to 7 and 03-30 to 0 to use the pulse input terminal PI as the frequency,
reference source, refer the figure 4.3.5.
(2) Set parameter 01-02 (maximum output frequency) and 03-27 (scale of pulse input terminal) PI
as the frequency source. Set parameter 03-34 (pulse input filter time) if the performance of
inverter is effected.
03-53 Current Agree Level 2
Range 【0.0~999.9】A