4-134
04-11 AO function setting
Range
【0】:Output frequency
【1】:Frequency command
【2】:Output voltage
【3】:DC voltage
【4】:Output current
04-12 AO gain
Range 【0.0~1000.0】%
04-13 AO bias
Range 【-100.0~100.0】%
04-15 AO Slope
Range
【0】:Positive
【1】:Nagetive
04-16 Proportio Gearing function
Range
【0】:Disable
【1】:Enable
For the analog output and related parameters, please refer to figure 4.3.50.
Figure 4.3.50 Analog outputs and related parameters
(1) Analog output adjustment (04-12, 04-13)
Use parameter 04-12 to select the analog output signal for AO and parameter 04-13 to adjust
the bias to AO.
Adjust the gain so that the analog output (10V) matches 100% of the selected analog output
signal.
Adjust the bias so that the analog output (0V/4mA) matches 0% of selected analog output
signal.
Please refer fig 4.3.51 for analog output level adjustment.
Figure 4.3.51 Analog output level adjustment