4-135
(2) Analog output terminal function selection (04-11)。
Please refer to the following table 4.3.33。
Table 4.3.33 Selection of analog output terminals function (04-11)
04-11
parameter
setting
Function
(Keypad display)
Monitoring
Parameters
12 Group
Control Mode
VF SLV PMSLV
0 Output Freq 12-17 O O O
1 Freq Ref 12-16 O O O
2 Output Voltage 12-19 O O O
3 DC Voltage 12-20 O O O
4 Output Current 12-18 O O O
(3) F-Gain(04-16):
Please refer fig 4.3.52 for F- Gain function, this function provides the facility for setting the
frequency reference to more than one inverter set by a master potentiometer then the master
frequency can be scaled by three individual potentiometers for each inverter as show in the
diagram below.
Please refer table 4.3.34, when 04-16=1 and 00-05=2, AI1 will be master signal, AI2 will be ratio
signal.
Figure 4.3.52 Example of F-Gain function
Table 4.3.34 Parameter setting of F-Gain
A B C
00-05=2 00-05=2 00-05=2
00-12=100 00-12=200 00-12=50
04-16=1 04-16=1 04-16=1
Figure 4.3.53 Diagram of F-Gain function