4-136
04-20 AO signal scanning and filtering time
Range 【0.00~0.50】Sec
Setting of parameter 04-20 is used for filtering momentary change in analog output signal.
When it is enabled, system response will lower down and interference protection will enhance.
04-22 AO Voltage Correction Selection
Range 【0~1】
This function is used for analog voltage correction. Normally, analog voltage does not need to
be correction. If necessary, please connect AO and AI2 terminal and set 04-22=1, inverter will
execute analog voltage correction. 04-22 will be cleaned to 0 automatically when voltage
correction function finished.