7-42
Cn041.2 Turret mode return to zero function
【
5-5
】
Initial Value Unit Setting Range Effective Cn029 Reset
0 -- 0 ~ 1 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
002CH 2029H 2029H -- -- O --
--
Setting Description:
Setting Description
0 Not Functioning
1
The driver execute turret return to zero function after
setting as 1; will automatically clear the setting to 0 after
completed.
Cn041.3 Current position return to zero
Initial Value Unit Setting Range Effective Cn029 Reset
0 -- 0 ~ 1 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
002CH 2029H 2029H O O O O
O
Setting Description:
Setting Description
0 Not Functioning
1
The driver execute position return to zero function after
setting as 1; will automatically clear the setting to 0 after
completed.
Cn043 Analog monitoring output MON1 output proportion
JSDG2S-E does not
have this function
【
5-6-11
】
Initial Value Unit Setting Range Effective Cn029 Reset
100 % -1000 ~ 1000 -- --
RS-485 CANopen EtherCAT Pi Pe Pt S T
002EH 202BH 202BH O O O O O
Setting Description:Take 10V/1.5x rotational speed = 100% as example, if the analog monitoring output proportion is
changed to 10V/0.75x rotational speed, set the parameter as 200%