6 Using the product
52
3. Evaluate measurement result: [], [] [OK].
- The measurement result is displayed
4. Save measurement result: [Save].
Options
> [Options] Show Graphic: a section of past measuring
values is displayed in a line graph (zoom function available [],
[]).
> [Options] Manometer: The measuring values are displayed
in the same way.
> [Options] Factory setting: the values are reset to the
default settings.
> [Options] Overall graphic curve: the measuring values
across the overall measuring time are displayed in a line graph.
6.2.5.2. Main test
Immediately prior to commissioning and following the pressure test,
all pipelines, going as far as the closed instrument connectors of
the gas appliances, must be tested for tightness using air at an
overpressure of 150 mbar (TRF 2012). The pipelines are deemed
leak-proof if, following temperature equalisation, the test pressure
does not drop throughout the subsequent 10 minute duration of the
test.
Calling up the function:
> [] Measurements [OK] Liquid gas (TRF) Main
test [OK].
Setting parameters
Parameter Explanation
Stability time Set stability time
Measurement period Set measurement period
TRF 2012 stipulates a
measurement period of 10 min.
Test pressure (target) Set test pressure
According to TRF 2012, the test
pressure is 150 mbar.
1. Edit values: [Edit].
2. Enter values. [], [] and sometimes [], [] [OK].