6 Using the product
62
Option
> End stability time early: [Next]
> End measurement period early: [Next]
- Measurement is cancelled.
- Pressure test is ended.
3. Evaluate measurement result: [], [] [OK].
- The measurement result is displayed
4. Save measurement result: [Save].
Options
> [Options] Show Graphic: a section of past measuring
values is displayed in a line graph (zoom function available [],
[]).
> [Options] Manometer: The measuring values are displayed
in the same way.
> [Options] Overall graphic curve: the measuring values
across the overall measuring time are displayed in a line graph.
> [Options] Settings: The type of test (reference
pressure/operating pressure) can be set and the reference
pressure of 23 mbar is displayed
6.2.7. Waste water (DIN EN 1610) with air
Calling up the function:
> [] Measurements [OK] Waste water [OK].
Setting parameters
Parameter Explanation
Test method Select test method
Pipe material Select pipe material
Nominal diameter Select nominal diameter
Stability time Set stability time
Measurement period Set measurement period
Test pressure (target) Set test pressure
1. Edit values: [Edit].
2. Enter values. [], [] and sometimes [], [] [OK].