6 Using the product
60
> [Options] → Settings: The type of test (reference
pressure/operating pressure) can be set and the reference
pressure of 23 mbar is displayed.
6.2.6.3. Test with water
A high pressure probe is required for this test.
Calling up the function:
> [] → Measurements → [OK] → Drinking water → Test
with water → [OK].
Setting parameters
Parameter Explanation
Pipe material Select pipe material
Crimp connection Enable/disable
Stability time Set stability time
The ZVSHK sheet as per DIN EN
806-4 stipulates a stability time of
30 min if there is a significant
difference between the ambient
and water temperature.
Measurement period Set measurement period