3. Wiring
1.
How to wire
3-6
TSC
Use one machine of TSC (with reset switch)
Even if the emergency stop switch is released, the motor would not be energized until the
reset switch is turned ON.
The reset switch must be turned ON when the power is turned ON.
Use the external relay CR with the surge absorption diode at 0.1 A or less coil current.
Connecting TDO will open the internal relay K1, and the TDO emergency stop switch is
activated.
When TDO is not connected, the internal relay K1 will be closed.
When connecting TSC to the network unit TNU, do not wire the CN5 pin number
(S1).
(Doing so may cause fault.)
24V
0V
S1
S2
MPO
MPI
24V
0V
EMG-
TDO
0V
Emergency
stop switch
CN4
CN3
K1
TSC
CR
X
X
CR
CR
Reset
switch