TSC 800 TRANSFER SWITCH CONTROLLER
PM 049 REV 10 08/09/25 Thomson Technology
11
LCD viewing window. The LCD display is mounted on the main PCB which is visible
from the lexan faceplate.
EXIT pushbutton. The EXIT function is used to scroll backwards through the status
menus or programming prompts to the previous item. The EXIT function is used to
“exit” the programming menu by holding this button down for approximately 2 seconds
while in the programming mode.
DECREMENT pushbutton. The DECREMENT function is used to change a
programming value while in the programming mode. When this pushbutton is held
down, the displayed value will be “decremented” to a lower value as desired. NOTE:
The longer the pushbutton is held down, the faster the value will be decremented.
INCREMENT pushbutton. The INCREMENT function is used to change a
programming value while in the programming mode. When this pushbutton is held
down, the displayed value will be “incremented” to a higher value as desired. NOTE:
The longer the pushbutton is held down, the faster the value will be incremented.
ENTER pushbutton. The ENTER function is used to scroll forwards through the status
menus or programming prompts to the next item. The ENTER function is used to
“enter” and accept new programming or operating mode changes after a new value
has been selected (NOTE: Pressing the Exit button instead of the Enter button will
reject the newly selected value and retain the original value). NOTE: In the
programming mode, the longer the ENTER pushbutton is held down, the faster the
next menu prompt will appear.
Load on Utility supply LED light viewing window
Load on Generator supply LED light viewing window
NOTE: A lamp test feature is provided to test all LED lights as well as the LCD display.
To activate the lamp test feature, simultaneously push the INCREMENT and
DECREMENT pushbuttons. All LEDs and LCD display pixels should illuminate for
approximately 2 seconds then return to their original status. The Lamp Test feature is
also used to clear active fault conditions and return the controller to normal operation.
NOTE: An active Timer Bypass feature is provided to allow a manual initiated bypass.
To activate the feature, simultaneously push the DECREMENT and ENTER
pushbuttons. The previously bypassed timer will operate normally during its next
cycle. Refer to Timer Bypass section for related timers.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the THOMSON TSC 800 - V2.2 and is the answer not in the manual?

THOMSON TSC 800 - V2.2 Specifications

General IconGeneral
BrandTHOMSON
ModelTSC 800 - V2.2
CategoryController
LanguageEnglish

Related product manuals