EasyManua.ls Logo

Thytronic SIF5600 - Page 89

Thytronic SIF5600
96 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
89
89
SIF5600 - Manual - 03 - 2008
Framing:
INT [ 1] tTR2 (1=10 ms)
1,99 step 1
100
default: 20
Dimension : 1 register
Synopsis : class WREG -> ADR=16 (NUM=17), DIM=1
WREG NUM=18 Description : K3 configuration
Framing:
B32 [ 1] K3
bit 0 Self test
bit 1 PW break Blin1
bit 2 CB fail
bit 3 PW shorted
bit 4 Start I>
bit 5 Start I>>
bit 6 Start IE>
bit 7 Start IE>>
bit 8 Trip I>
bit 9 Trip I>>
bit 10 Trip IE>
bit 11 Trip IE>>
bit 12 Open 52
bit 13 Close 52
bit 14 Self test 52
default: 0x00000000
ENUM[ 3] K3 mode
0 DeEn-NoLatch
1 DeEn-Latch
2 En-NoLatch
3 En-Latch
default: 0
Dimension : 3 registers
Synopsis : class WREG -> ADR=17 (NUM=18), DIM=3
WREG NUM=19 Description : K3 timer
Framing:
INT [ 1] tTR3 (1=10 ms)
1,99 step 1
100
default: 20
Dimension : 1 register
Synopsis : class WREG -> ADR=18 (NUM=19), DIM=1
WREG NUM=20 Description : K4 configuration
Framing:
B32 [ 1] K4
bit 0 Self test
bit 1 PW break Blin1
bit 2 CB fail
bit 3 PW shorted
bit 4 Start I>
bit 5 Start I>>
bit 6 Start IE>
bit 7 Start IE>>
bit 8 Trip I>
bit 9 Trip I>>
bit 10 Trip IE>
bit 11 Trip IE>>
bit 12 Open 52
bit 13 Close 52
bit 14 Self test 52
default: 0x00000000
ENUM[ 3] K4 mode
0 DeEn-NoLatch
1 DeEn-Latch
2 En-NoLatch
3 En-Latch
default: 0
Dimension : 3 registers
Synopsis : class WREG -> ADR=19 (NUM=20), DIM=3
WREG NUM=21 Description : K4 timer
Framing:

Table of Contents