90
90
SIF5600 - Manual - 03 - 2008
INT [ 1] tTR4 (1=10 ms)
1,99 step 1
100
default: 20
Dimension : 1 register
Synopsis : class WREG -> ADR=20 (NUM=21), DIM=1
WREG NUM=22 Description : I> protection
Framing:
ENUM[ 1] I curve
0 Independent
1 Curve A
2 Curve B
3 Curve C
default: 0
Dimension : 1 register
Synopsis : class WREG -> ADR=21 (NUM=22), DIM=1
WREG NUM=23 Description : I> indep
Framing:
INT [ 1] I> indep (1000=1 In)
100,999 step 1
1000,10000 step 10
default: 1000
Dimension : 1 register
Synopsis : class WREG -> ADR=22 (NUM=23), DIM=1
WREG NUM=24 Description : t> indep
Framing:
INT [ 1] t> indep (1=10 ms)
5,99 step 1
100,999 step 1
1000,9990 step 10
10000,18000 step 100
default: 40
Dimension : 1 register
Synopsis : class WREG -> ADR=23 (NUM=24), DIM=1
WREG NUM=25 Description : I> dep
Framing:
INT [ 1] I> dep (1000=1 In)
100,999 step 1
1000,2500 step 10
default: 1000
Dimension : 1 register
Synopsis : class WREG -> ADR=24 (NUM=25), DIM=1
WREG NUM=26 Description : t> dep
Framing:
INT [ 1] t> dep (1=10 ms)
10,99 step 1
100,999 step 1
1000,6000 step 10
default: 100
Dimension : 1 register
Synopsis : class WREG -> ADR=25 (NUM=26), DIM=1
WREG NUM=27 Description : I>> indep
Framing:
INT [ 1] I>> indep (1000=1 In)
100,999 step 1
1000,9990 step 10
10000,20000 step 100
default: 7000
Dimension : 1 register
Synopsis : class WREG -> ADR=26 (NUM=27), DIM=1
WREG NUM=28 Description : t>> indep
Framing:
INT [ 1] t>> indep (1=10 ms)
3,99 step 1
100,1000 step 1
default: 3
Dimension : 1 register
Synopsis : class WREG -> ADR=27 (NUM=28), DIM=1