EasyManuals Logo

Toptech RCU II DIV2 User Manual

Default Icon
93 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #48 background imageLoading...
Page #48 background image
39
MultiLoad II Analog Wiring
5.4.4
5.4.4.1 RTD Wiring
I/O DIGITAL/
ANALOG
I/O 2 METER
METER 0 METER 1
RTD
RTD.V+
RTD
100Ω
°C
Pt
°F
100Ω
°C
Pt
°F
100Ω
°C
Pt
°F
α=0.00385
100 Ω
α=0.00385
100 Ω
α=0.00385
100 Ω
RTD
RTD.R+
RTD.R-
RTD.COM
RTD.V+
RTD.R+
RTD.R-
RTD.COM
RTD.V+
RTD.R+
RTD.R-
RTD.COM
V+ 1
R+ 2
R- 3
COM 4
IO_DA TB4
RTD
V+ 1
R+ 2
R- 3
COM 4
IO_2M TB5
RTD
V+ 1
R+ 2
R- 3
COM 4
IO_2M TB4
RTD
Note: All 4 wires MUST be run to the sensor. Do not simply jumper REF- to COM or REF+ to V+ at the FCM II. For 3-wire and 2 wire probes, the
connection of REF- to COM and REF+ to V+ should be as close as possible to the probe (within inches).