102 HX7+ ASD Installation and Operation Manual
VI/II Speed Frequency #1
Program Frequency Setting Speed Reference Setpoints VI/II
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control mode.
See VI/II Speed Reference #1 (F201) for further information on this setting.
This parameter sets VI/II Speed Frequency #1 and is the frequency that is
associated with the setting of VI/II Speed Reference #1 while operating in the
Speed Control mode.
Direct Access Number — F202
Parameter Type — Numerical
Factory Default 0.0
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
VI/II Speed Reference #2
Program Frequency Setting Speed Reference Setpoints VI/II
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
See VI/II Speed Reference #1 for further information on this setting when
used for Speed control or Torque control.
This parameter sets the VI/II input level that is associated with VI/II Speed
Frequency #2 while operating in the Speed control mode or is associated with
the VI/II Torque Reference Setpoint #2 while operating in the Torque control
mode.
Direct Access Number — F203
Parameter Type — Numerical
Factory Default 100.00
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 100.0
Units — %
VI/II Speed Frequency #2
Program Frequency Setting Speed Reference Setpoints VI/II
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Speed
Control mode.
See VI/II Speed Reference #1 for further information on this setting when
used for Speed control.
This parameter sets the output frequency that is associated with VI/II Speed
Reference #2 setting while operating in the Speed control mode.
Direct Access Number — F204
Parameter Type — Numerical
Factory Default 80.00
Changeable During Run — Ye s
Minimum — 0.0
Maximum — Max. Freq. (F011)
Units — Hz
VI/II Torque Reference Setpoint #1
Program Torque Setting Setpoints VI/II
This parameter is used to set the gain and bias of the VI/II input terminal when
the VI/II terminal is used as the control input while operating in the Torque
Control mode.
This is accomplished by establishing an associated V/f output pattern for a
given VI/II input level.
See VI/II Speed Reference #1 for further information on this setting.
This parameter sets VI/II Torque Reference Setpoint #1 and is the output
torque value that is associated with the setting of VI/II Speed Reference #1
while operating in the Torque control mode.
Direct Access Number — F205
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 250.0
Units — %
F202 F205