114 HX7+ ASD Installation and Operation Manual
BIN Speed Reference #1
Program Frequency Setting Speed Reference Setpoints BIN
This parameter is used to set the gain and bias of the binary input when the
discrete input terminals are used as the control input while operating in the
Speed Control mode or the Torque Control mode.
BIN Input Control Setup
Perform the following setup to allow the system to receive control input at the
binary input terminals:
•Program Fundamentals Standard Mode Selection Frequency
Mode #1 Use Binary/BCD Input.
•Program Fundamentals Standard Mode Selection Command
Mode Use Terminal Board.
•Program Terminal Selection Input Terminals; select and set the
desired discrete input terminals to Binary Bit(s) 0 – 7 (or 0 – MSB) (see
Table 14 on pg. 189). The binary input can control the direction, speed,
and/or torque of the motor.
Note: 255
D
is the decimal equivalent of the 8-bit BIN word with all input
terminals set to one (255 decimal = 11111111 binary).
BIN Speed Control Setup
•Set BIN Speed Reference #1 (F228) — the input signal that represents
BIN Speed Frequency #1.
•Set BIN Speed Frequency #1 (F229).
•Set BIN Speed Reference #2 (F230) — the input signal that represents
BIN Speed Frequency #2.
•Set BIN Speed Frequency #2 (F231).
•Provide a Run command (F and/or R).
Once set, as the binary input signal changes, the output signal of the ASD will
vary in accordance with the above settings.
This parameter sets BIN Speed Reference #1 and is the input signal that is
associated with the setting of BIN Speed Frequency #1 while operating in the
Speed Control mode.
BIN Torque Control Setup
•Set BIN Speed Reference #1 (F228) — the input signal level that
represents BIN Torque Reference Setpoint #1.
•Set BIN Torque Reference Setpoint #1 (F232).
•Set BIN Speed Reference #2 (F230) — the input signal level that
represents BIN Torque Reference Setpoint #2.
•Set BIN Torque Reference Setpoint #2 (F233).
•Provide a Run command (F and/or R).
Once set, as the binary input signal changes, the output signal of the ASD will
vary in accordance with the above settings.
This parameter sets BIN Speed Reference #1 and is the input signal that is
associated with the setting of BIN Torque Reference Setpoint #1 while
operating in the Torque Control mode.
Direct Access Number — F228
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.0
Maximum — 100.0
Units — %
Frequency Settings
Torque Settings
F228 F228